Addressable control device with integrated fire detection module for one extinguishing area (e.g
CO2, FM 200, Hi Expansion foam, Water Mist and Inert Gas, etc.) compliant with VdS 2496 and
EN 12094-1. The extinguishing panel 8010 is an electronic control device for extinguishing
systems with integrated fire detection module, compatible with series 9200 and IQ8Quad
detectors. It is additionally provided with respective detection zones for manual alarm, post flooding
and emergency stop as well as two zones for extinguishing system fault. Complex control functions
can be realized by using the 13 control groups (relays). Up to 8 extinguishing areas on the
esserbus of the fire detection system communication transponders (optional). A maximum of 16
communication transponders can be networked for each FACP 8000 C/M, IQ8Control 8000, or
IQ8Control via the (Part No. 808615)
Features
• ۱ Extinguishing area for max. 1,600 m² acc. to
VdS
• ۸ detector zones for up to 30 series 9200 and
IQ8Quad automatic detectors each (for twodetector
dependency up to 25 detectors)
• ۱ zone for manual alarm
• ۱ zone for emergency stop
• ۱ zone for post flooding
• ۱ zone for extinguishing system fault
• ۱ zone for blocking extinguishing system
• ۱ control input for buzzer OFF
• ۱ control input for control panel reset
• ۸ relays, monitored or floating 30V DC/2A
• ۳ relays, floating 30V DC/2A
• ۲ mains voltage relays, floating 230V AC/2A
• All outputs are provided with fuses
۳- DOWNLOAD OPERATING INSTALLATION MANUAL
جهت راه اندازی پانل های اطفا حریق esser لطفا با ما تماس حاصل فرمایید