Basic set for assembly of a FACP with module slots and software support of 2 modules. The modular FACP FlexES Control concept offers three pre-configured, factory-made expansion units (FX2, FX10, FX18) for operating up to 2, 10 or 18 modules. The FlexES Control expansion can, however, also be adapted to individual requirements by using separately provided components. Depending on the system’s design, it might be necessary to use an expansion housing unit for the batteries and an additional power supply unit. The FlexES system provides a Master & Slave Control Module (CPU), galvanically isolated loop modules and up to three cascadable and redundant Power Supply Units each with 150W (same or different main). As well it’s delivered with a dust filter, which is proven in use in typical applications with dust-laden environment and/or sanddust regions. System supports up to 254 digital loop addresses in total. Configuration is modularly expandable up to 10/18 loops by exchange of the CPU license and housing extensions
Features
• Combinable loop/spur technology with decentralized intelligence
• Freely configurable functionality of modules
• ۴ free programmable potential free contacts and 1 output for alarm transmission unit (ATU)
• Increased availability via emergency mode function of the loop modules
• Emergency mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the German Planning standard VDE 0833 and/or VdS 2095
• USB, RS 485, TTY interfaces onboard
• Direct output of the proprietary EDP communications protocol (Data Protocol) via interface R 485
• Operation of loop-powered alarm signaling devices (optical/acoustic/voice) in different alarm zones via esserbus-PLus
• Cascadable power supply to 450 W according to EN 54-4
• Loop length up to 3.5 km (esserbus)
• Operation of different input/output gateways
• Integrated interfaces for operation of required fire brigade periphery, e.g. fire brigade indicating
panel, fire brigade operating unit
• Event memory with 10,000 entries
• Operation of VdS-approved wireless components with convenient field intensity measurement
• Parameterization, calibration and programming directly via USB
• Galvanic isolation of analog loops possible
• Up to 1,000 control zones
جهت راه اندازی پانل های اعلام حریق FLEXES لطفا با ما تماس حاصل فرمایید.